STATIX Free calculators
Learn › RC Design 1 (Eurocode) › Lesson 3
Course · lesson 3 of 8

Shear and links

How a beam carries shear to EN 1992-1-1 6.2, on the Eurocode 2 route of the STATIX RC beam calculator: the concrete resistance VRd,c, the truss with a variable strut angle, designed links VRd,s, strut crushing VRd,max, and the minimum links and spacing.

1. Learning outcomes

After this lesson you can:

  • find the design shear at d from the face of a support;
  • work out VRd,c and decide whether designed links are needed;
  • explain the truss model and the limits on the strut angle;
  • size links for VRd,s and check the struts against VRd,max;
  • apply the minimum link ratio and the spacing limits.

2. Before you start

The values this lesson uses are those of the calculator’s Eurocode 2 route: the recommended CRd,c = 0.18/γc, vmin, ν1 and the cot θ range 1 to 2.5, with cot θ = 2.5 used for the links; αcc 1.0 for shear; z = 0.9d; the minimum link ratio 9.5N and the spacing 9.6N and 9.8N. The links are taken as B500 (fywk = 500 MPa).

3. How a beam carries shear

+V−Vshear force: largest at the supports, zero at mid-spanlinkslinks
Where the shear is. Under a uniform load the shear force falls in a straight line from the supports to zero at mid-span. The design shear is taken at a distance d from the face of the support, where a direct load is near the support (6.2.1(8)).
a diagonal crack opens; the links that cross it hold it shut
Shear cracks. Near the supports the beam cracks on a slope. The concrete between the cracks acts as inclined struts, and the links that cross a crack act as ties.
the truss: concrete struts at θ, links as ties, z = 0.9d
The truss model. EN 1992-1-1 6.2.3 treats a beam with links as a truss: compression struts at an angle θ, the links as vertical ties, and the top and bottom chords a lever arm z = 0.9d apart.

4. The resistances

VRd,c = [CRd,c k (100 ρ1 fck)1/3] bw dCRd,c0.18/γc = 0.12k = 1 + √(200/d)≤ 2.0ρ1 = Asl/bwd≤ 0.02not less than vmin = 0.035 k3/2 √fck (6.2.2(1))
The shear the concrete carries. Without designed links, a beam carries VRd,c: more with more tension steel, less in deep members (the size factor k). The calculator uses the recommended CRd,c 0.18/γc and vmin.
VEd ≤ VRd,cminimum linksVEd > VRd,clinks carry all of VEdin a beam, VRd,c is not added to the linksand every beam has at least the minimum links (9.2.2(5))
The decision. If the design shear is above VRd,c, the links must carry the whole of it: the Eurocode does not add the concrete contribution to the links, as some other codes do. Beams always get at least the minimum links.
θcot θ from 1.0 to 2.5(6.7N: 45° to 21.8°)flatter strut: fewer links,more load on the strut
The strut angle. The designer may choose θ within limits: a flatter strut (cot θ up to 2.5) crosses more links, so fewer are needed, but it squeezes the concrete harder. The calculator starts from cot θ = 2.5, the flattest the code allows.
VRd,s = (Asw/s) z fywd cot θ (6.8)Asw/s = VEd / (z fywd cot θ)Asw = two legs of the link2Y10 = 157 mm²; fywd = fywk/1.15
Designed links. The links that cross the strut zone over a length z cot θ carry the shear. A two-leg Y10 link gives Asw = 157 mm²; with B500 links fywd = 434.8 MPa.
VRd,max = bw z ν1 fcd / (cot θ + tan θ) (6.9)ν1 = 0.6(1 − fck/250)the cracked web is weakerfcd with αcc 1.0for shear, on this routeif VEd > VRd,max at cot θ 2.5, use a steeper strut; at cot θ 1, a bigger web
Crushing the struts. However many links there are, the concrete struts can crush. VRd,max is largest at θ = 45°. The calculator’s checks take fcd with αcc 1.0 for shear (bending uses 0.85).

5. Minimum links, spacing and zones

ρw,min = 0.08 √fck / fywk (9.5N)Asw/s ≥ ρw,min bws ≤ 0.75 dalong the beam (9.6N)legs ≤ 0.75 d, 600across the beam (9.8N)
Minimum links and spacing. Every beam has links at least at the minimum ratio, and no further apart than 0.75d along the beam, so that every possible shear crack crosses at least one link.
closerminimumcloserzones: designed links near the supports, minimum links in the middle
Link zones. Since the shear falls towards mid-span, a beam usually has closer links near the supports and the minimum in the middle. The calculator’s detailing lays the links in zones like this.
ΔFtd = 0.5 VEd cot θthe shift rule: the tension bars carry more near the supports (9.2.1.3)
Shear adds tension. The truss pulls the bottom bars harder than the bending moment alone suggests. EN 1992-1-1 allows for this by shifting the moment curve by al = z cot θ/2 when the bars are curtailed and anchored (lesson 8).

6. Example A: the lesson 1 beam

The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.

7. Example B: a heavily loaded beam

The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.

8. Do it in STATIX

The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.

9. Common mistakes

The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.

10. Exercises

The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.

11. Self-check quiz

The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.

12. Lesson 3 on one page

The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.

Next: Lesson 4, deflection and crackingSpan over depth, long-term deflection, bar spacing and crack width.
Go to lesson 4

A worked example for learning, not a design. Check every value against the current code and your own project, and have the design checked and signed by a registered professional engineer.