STATIX Free calculators
Learn · worked example

Punching shear in flat slabs to SANS 10100

A 400 mm square interior column in a 250 mm flat slab: effective shear, the column-face check, vc, control perimeters at 0.75d steps and shear links. Every number below comes from the free STATIX punching shear calculator and was checked by hand.

1. The problem

InputValue
Column400 × 400 mm, interior
Slab250 mm flat slab, no drop panel, cover 25 mm
Top steel over the columnY16 at 125 mm both ways
Design shear from the slab into the columnVt = 800 kN (ultimate), no unbalanced moment
Materialsfcu = 30 MPa, fyv = 450 MPa for the links
Plan of the control perimeters with rings of shear link legs around a 400 mm column, and a section through the slab, from the STATIX punching shear calculator
The free punching shear calculator with these inputs: the control perimeters and the rings of link legs on plan, and the section through the slab.

2. Effective depth and steel ratio

The two layers of top steel sit at different depths. SANS 10100 cl. 4.4.5.2.1 uses the average depth of the steel that crosses the perimeter.

dx = 250 − 25 − 16/2 = 217 mm dy = 250 − 25 − 16 − 16/2 = 201 mm d = (217 + 201) / 2 = 209 mm As = Y16 at 125 = 1,608 mm²/m each way 100As/(bd) = 100 × 1,608 / (1000 × 209) = 0.77 (the same both ways, so the average is 0.77)

3. Concrete shear stress vc (cl. 4.3.4.1, eq. 2)

vc = (0.75/γm) × (fcu/25)1/3 × (100As/bd)1/3 × (400/d)1/4 = (0.75/1.40) × (30/25)1/3 × 0.771/3 × (400/209)1/4 = 0.536 × 1.063 × 0.916 × 1.176 = 0.614 MPa

SANS uses 0.75 with γm = 1.40. BS 8110 uses 0.79 with 1.25, which gives a higher vc. Do not mix the two. fcu is capped at 40 MPa and 100As/bd at 3.

4. Effective shear with moment transfer (cl. 4.6.2.2)

A column in a flat slab also takes some moment from the slab, which makes the shear uneven around it. For an interior column in a braced building with spans that differ by no more than 25%, SANS lets you allow for this with a factor of 1.15.

Veff = 1.15 Vt = 1.15 × 800 = 920 kN

In other cases use eq. (8): Veff = Vt(1 + 1.5Mt/(Vtx)), but not less than 1.15Vt, where x is the side of the perimeter parallel to the bending axis. Corner columns, and edge columns bent at right angles to the edge, use 1.25Vt. Edge columns bent parallel to the edge use 1.40Vt (cl. 4.6.2.3).

5. Column face

u0 = 2 × (400 + 400) = 1,600 mm v0 = Veff / (u0 d) = 920,000 / (1,600 × 209) = 2.75 MPa vmax = lesser of 0.75√fcu and 4.75 MPa = 0.75 × √30 = 4.11 MPa (cl. 4.4.5.2.2) 2.75 ≤ 4.11 MPa OK (67%)

This is the concrete crushing next to the column. No links can fix it: if it fails, the slab, a drop panel or the column must get bigger.

The calculator uses the general limit for a concentrated load on a slab, 0.75√fcu. For the face of a column in a flat slab, cl. 4.6.2.4 allows the lesser of 0.8√fcu and 5.0 MPa, here 4.38 MPa. The calculator's check is on the safe side.

6. Control perimeters (cl. 4.4.5.2)

The first perimeter is the rectangle 1.5d from the column face. If v there is more than vc, check further perimeters at 0.75d steps until one passes. For a rectangle around a rectangular column the length is u = 2(cx + cy) + 8a, where a is the distance from the face.

v = Veff / (u d) (eq. 7) Perimeter 1 at 1.5d = 314 mm: u = 1,600 + 8 × 313.5 = 4,108 mm; v = 920,000 / (4,108 × 209) = 1.072 MPa
Perimeteru (mm)v (MPa)v / vc
1 at 1.50d = 314 mm4,1081.0721.75: links needed
2 at 2.25d = 470 mm5,3620.8211.34: links needed
3 at 3.00d = 627 mm6,6160.6651.08: links needed
4 at 3.75d = 784 mm7,8700.5590.91: OK, no links

All three failing perimeters are below 2vc = 1.23 MPa, so links are allowed. The slab is 250 mm thick, over the 200 mm that eq. 7(a) and 7(b) require.

Without links, this slab would carry Vt = 0.614 × 4,108 × 209 / 1.15 = 458 kN on this column. The 800 kN here is well above that.

7. Shear links (cl. 4.4.5.2.6)

Which formula applies depends on how far v is above vc:

vc < v ≤ 1.6vc (0.98 MPa): ΣAsv ≥ (v − vc) u d / (0.87 fyv), with (v − vc) at least 0.4 MPa (eq. 7a) 1.6vc < v ≤ 2vc: ΣAsv ≥ 5(0.7v − vc) u d / (0.87 fyv) (eq. 7b) 0.87 fyv = 0.87 × 450 = 391.5 MPa (fyv may not be taken above 450 MPa) Perimeter 1: v = 1.072 > 0.98, so eq. 7b ΣAsv = 5 × (0.7 × 1.072 − 0.614) × 4,108 × 209 / 391.5 = 1,496 mm² Perimeter 2: v − vc = 0.21 < 0.4, so use 0.4 ΣAsv = 0.4 × 5,362 × 209 / 391.5 = 1,145 mm² Perimeter 3: v − vc = 0.05 < 0.4, so use 0.4 ΣAsv = 0.4 × 6,616 × 209 / 391.5 = 1,413 mm²

Each perimeter's steel goes in its failure zone, the band between it and the line 1.5d inside it. The calculator spreads it over at least two rings of links in that zone. Links already in the zone from an earlier perimeter count.

8. Link layout

Rings at 0.5d, then at no more than 0.75d = 157 mm apart: 105, 261, 418 and 575 mm from the face Zone of perimeter 1 (0 to 314 mm): rings at 105 and 261 Zone of perimeter 2 (157 to 470 mm): rings at 261 and 418 Zone of perimeter 3 (314 to 627 mm): rings at 418 and 575 20 Y10 legs per ring = 20 × 78.5 = 1,571 mm² ≥ 1,496 mm² Spacing along the ring: 4,108 / 20 = 205 mm on perimeter 1; 310 mm on the outer ring at 575 mm; both ≤ 1.5d = 314 mm

The calculator puts the full ΣAsv of the worst perimeter in every ring. That is more than each zone needs: each zone gets two rings, so 3,142 mm² against 1,496 mm² at most. You can reduce the legs once you have checked each zone. Anchor every leg around the top steel.

9. Result

CheckResult
Column face2.75 ≤ 4.11 MPa
First perimeter (1.5d)1.072 > vc 0.614 MPa: links needed
Links needed out toperimeter 3 at 3.0d; perimeter 4 at 3.75d passes (0.559 MPa)
Link steel1,496 / 1,145 / 1,413 mm² on perimeters 1 / 2 / 3
Layout4 rings of 20 Y10 legs, first at 105 mm, then every 157 mm

Two rules the calculator applies that matter for other inputs. In flat slabs between 150 and 200 mm thick, SANS cl. 4.6.2.1 reduces the stress in the links in a straight line from the full value at 200 mm to zero at 150 mm, and cl. 4.6.1.5 sets 150 mm as the thinnest slab that may have shear reinforcement. So a thinner slab that needs links fails the check. And fyv is never taken above 450 MPa, even if the link steel is stronger.

Run this example yourselfThe free STATIX punching shear calculator opens with exactly these inputs. Change the load, slab depth or steel and every perimeter and link updates, with a printable calc sheet.
Open the free punching shear calculator

A worked example for learning, not a design. Check every value against the current code and your own project, and have the design checked and signed by a registered professional engineer.

Early access

Be first to use STATIX 3D and STATIX 2D.

Leave your email and we will tell you when each part is ready for testing. One confirmation now, one message then. A short monthly update only if you tick the box.