Masonry wall design to SANS 10164
A masonry wall is strong in compression but weak in tension, so the design is about how straight the load path stays. A load that sits off-centre (eccentric), and a tall thin wall that bows out, both reduce the compression the wall can carry. Wind on the face bends the wall like a slab supported on its edges, which the bond of the mortar must resist. Every number below comes from the free STATIX masonry wall calculator with the inputs in step 1.
1. The problem
| Input | Value |
|---|---|
| Design code | SANS 10164-1 |
| Design type | Unreinforced wall |
| Construction | Single leaf |
| Thickness t | 190 mm |
| Clear height h | 2700 mm |
| Effective height ρ | 0.75 — enhanced (RC floor/roof both ends) |
| Unit | Standard format brick — Table 3(a) |
| Unit height for the δ helper | 73 mm (standard brick) |
| Unit width least horizontal size | 106 mm (standard brick) |
| 90 × 90 modular brick SANS 10164-1 4.2.2.2(c) | No — standard format (222 × 106 × 73) |
| Unit strength fu | 14.0 MPa |
| Mortar class | Class II — 7.0 |
| Axial NEd ULS | 120 kN/m |
| Eccentricity ex | 7.0 mm |
| Panel length L | 3.6 m |
| Wind Wk | 0.7 kPa |
2. Masonry strength f_k
The characteristic strength of the wall depends on the strength of the units (bricks or blocks), their shape and the mortar class. It is read from the code tables and adjusted for small areas or unit format where needed.
3. Slenderness and eccentricity
The effective height depends on how the wall is held at top and bottom; the effective thickness on its build-up. Their ratio is the slenderness, which has a limit. The load eccentricity, plus the extra eccentricity from the wall bowing, gives a capacity reduction factor β.
4. Vertical load capacity
The design capacity per metre is β × t × f_k / γ_m. It must be at least the design vertical load.
5. Wind on the face
Wind pushes on the face of the wall; it spans between its supports like a two-way slab. The wall is much stronger bending across the bed joints (perpendicular) than along them (parallel); the ratio μ shares the moment between the two directions, using a bending moment coefficient α.
Cavity walls share the load between the leaves; Eurocode 6 uses a capacity factor Φ instead of β. The calc sheet shows the route chosen.
Open the masonry wall calculator
A worked example for learning, not a design. Check every value against the current code and your own project, and have the design checked and signed by a registered professional engineer.