Masonry lintel design to SANS 10164
Masonry over an opening does not all sit on the lintel. Once the mortar has set, the brickwork arches over the opening, so the lintel carries only a triangle of masonry above it, plus any floor or point load that lands inside that triangle's zone. Loads higher up go round the opening into the walls. That is why a lintel can be much smaller than the wall above suggests, as long as there is enough masonry above and beside the opening for the arch to form. Every number below comes from the free STATIX lintel calculator with the inputs in step 1.
1. The problem
| Input | Value |
|---|---|
| Lintel type | Reinforced masonry lintel (SANS 10164-2) |
| Clear opening Lc | 1800 mm |
| Wall thickness | 230 mm |
| Bearing each end | 350 mm |
| Masonry above to the floor / roof | 2400 mm |
| Beside shorter side | 600 mm |
| Unit | Brick |
| Material | Burnt clay |
| Unit strength nominal | 14 MPa |
| Mortar class | II |
| Category manufacturing / construction | B / I |
| Slab / roof G / Q, characteristic | 8 kN/m |
| Slab or roof imposed line load kN per m | 2 kN/m |
| Slab bears | On the wall above |
| Cover to the bar | 40 mm |
| Infill concrete | Grade 25 |
| Exposure Table 17 | E1 |
| Steel corrosion rating Table 15, checked against Table 16 | C1 uncoated |
2. Effective span and the arch
The effective span runs a little past each face of the opening into the bearing. The masonry can only arch if there is enough height of wall above the opening and enough wall beside it (a pier); otherwise the whole height must be carried.
3. Loads on the lintel
The lintel carries its own weight, the masonry triangle (zero at the ends, largest at midspan) and any floor load or point load inside the load zone. The worst load combination gives the bending moment and the shear.
4. Bending
The lintel (with the masonry or concrete above it working with it, for a reinforced masonry lintel) must resist the moment. A deep lintel has a lower limit on span over depth.
5. Shear
Near the supports the shear stress must stay within what the masonry or concrete can carry.
6. Deflection and lateral stability
A lintel that sags cracks the masonry above, so span over effective depth is limited. A long, slender lintel must also not buckle sideways.
7. Bearing at the ends
The end reactions bear on the walls each side. The stress right under the lintel, and spread down to a depth below it, must stay within what the masonry can take.
8. Steel, cover and materials
Bar size and spacing, laps, anchorage at the ends, cover and corrosion protection, the infill grade and the masonry strength itself.
RC and precast lintels use the same load triangle; their bending, shear and deflection follow the concrete code. The calc sheet shows every formula.
Open the lintel calculator
A worked example for learning, not a design. Check every value against the current code and your own project, and have the design checked and signed by a registered professional engineer.