Deflection and crack control
A beam must not only be strong. It must also be stiff enough not to sag too much, and its cracks must stay fine. This lesson checks both with the quick SANS 10100-1 rules: span/effective depth and bar spacing.
1. Learning outcomes
After this lesson you can:
- explain why deflection and crack width matter, and why they grow with time;
- check a beam's span/effective depth ratio with the basic ratio and its modification factors;
- work out the service stress in the steel and the tension steel factor;
- apply the flange factor to T-beams;
- check the bar spacing for crack control, and read STATIX's long-term deflection and crack width results.
2. Before you start
- Lesson 1 (the rectangular beam) and lesson 2 (the T-beam): this lesson checks both.
- The free STATIX RC beam calculator, open in a second tab.
- A pocket calculator and about 50 minutes.
3. Why deflection matters
Lessons 1 to 3 made the beam strong enough at the ultimate load. That is the safety check. This lesson is about the beam in normal use, at the service load: the serviceability limit state.
A beam that sags a lot is not unsafe, but it is a nuisance. The sag also grows with time, because concrete creeps and shrinks.
4. The span/depth method (SANS 10100-1, 4.3.6)
Working out the sag of a cracked concrete beam by hand is long. For normal beams the code offers a short cut: limit the ratio of span to effective depth.
The allowed ratio is built from four factors:
For spans over 10 m there is a further reduction (SANS 10100-1, 4.3.6), and cantilevers need more care. This lesson stays with normal simply supported spans.
The tension steel factor
The bottom bars stretch as the beam bends. The harder they work at service load, the more the beam curves and sags. So the factor depends on two things: the steel's service stress fs, and how hard the section works, M/(b d²), with the ultimate moment M (SANS 10100-1, Table 11):
The service stress fs is the stress in the bars under the service load. It starts from the design stress and is scaled down twice:
This is a useful lesson in itself: adding a little more steel than needed lowers fs and lets the beam span further. A deeper beam does even better, because d appears in L/d and in M/(b d²).
The compression steel factor
Bars in the compression zone resist creep of the concrete there, so they reduce the long-term sag. SANS 10100-1 Table 12 gives a factor of 1.0 or more against 100As′/(b d). If you ignore small top bars, use 1.0: that is on the safe side.
The flange factor for T and L beams
A T-beam is very strong in bending for the size of its web, but its cracked web is not as stiff. So for flanged beams the allowed ratio is cut: by 0.8 when bw/beff ≤ 0.3, rising to 1.0 for a rectangle (SANS 10100-1, 4.3.6.5). In M/(b d²) STATIX uses the web width bw, which is on the safe side.
5. Crack control by bar spacing
Cracks are normal in reinforced concrete: the steel only starts to work once the concrete around it has cracked. What matters is that the cracks stay fine.
For normal beams the code does not ask you to calculate the crack width. Instead it limits how far apart the tension bars may be (SANS 10100-1, 4.11.8.2):
- The clear gap between bars near the tension face must not be more than the value in Table 25. It depends on fy (and on any moment redistribution).
- From a corner of the beam to the nearest bar, the clear distance must not be more than half of that value.
- Beams deeper than 750 mm also need side bars on the faces of the web.
6. What STATIX checks
When you run the RC beam calculator you get both: the quick span/depth check of this lesson, and the long-term deflection and crack width worked out from the cracked section. If they disagree, the calculation is the better answer; the span/depth rule is a safe short cut for normal beams.
7. Example A: the lesson 1 beam
The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.
8. Example B: the lesson 2 T-beam
The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.
9. Do it in STATIX
The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.
10. Common mistakes
The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.
11. Exercises
The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.
12. Self-check quiz
The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.
13. Lesson 4 on one page
The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.
Go to lesson 5
A worked example for learning, not a design. Check every value against the current code and your own project, and have the design checked and signed by a registered professional engineer.