Wind 2: pressure coefficients and a portal frame

Lesson 4 found the peak pressure qp. This lesson spreads it over the building: external coefficients for walls and roofs, internal pressure, the worst net pressures, local coefficients for cladding, and the line loads on a portal frame, with the STATIX wind load calculator.

1. Learning outcomes

After this lesson you can:

  • name the wall and roof zones and read Cpe from SANS 10160-3;
  • explain internal pressure and choose the worse Cpi for each element;
  • find net pressures, including the local values for cladding and fixings;
  • turn zone pressures into the wind loads on a portal frame;
  • check every zone in the STATIX wind load calculator.

2. Before you start

  • Lesson 4: the peak velocity pressure qp.
  • Your copy of SANS 10160-3 (clause 8.3, Tables 6 to 12) and the free wind load calculator.
  • A pocket calculator and about 50 minutes.

3. Walls

DEABCplan: D windward, E leeward; A, B, C along the sideswind
Wall zones (SANS 10160-3 8.3.2, Table 6). The windward wall D is pushed, the leeward wall E is sucked, and the side walls are sucked hardest near the windward corner (A), less further back (B, C). The zone widths depend on e = the smaller of b and 2h.
0DEh/d = 0.25h/d = 1Cpe of the windward and leeward walls
The coefficients change with the building's shape. For a squat building (small h/d) the windward wall gets a little less pressure and the leeward wall a little less suction; between the table's rows STATIX interpolates.

4. Roofs

FGFHJIwindF, G: e/10deep stripF: e/4 longJ: e/10past the ridge
Duo-pitch roof zones (Table 10, wind on the long face). The windward eave strip (F at the corners, G between) is sucked hardest, then H on the rest of the windward slope; J is a strip just past the ridge and I the rest of the leeward slope.
low pitchsteepwindward slope suckedwindward slope may be pushed
Roof pitch matters. On a low roof the whole roof is sucked up. On steeper roofs the windward slope can be pushed down, so Table 10 gives a negative and a positive set and both are separate load cases. STATIX lists both.
windmono-pitch: Tables 8 and 9zones depend on which eave faces the wind:the low eave, the high eave, or the side
Mono-pitch roofs have their own tables (8 for wind on the low or high eave, 9 for wind along the slope). Hipped roofs use Table 12. The STATIX calculator offers duo-pitch, mono-pitch and hipped roofs, and flat roofs below 5°.

5. Internal pressure and net pressure

internal pressure acts on every inside faceCpi: +0.2 / −0.3 (both checked), or from the openings
Internal pressure. Air leaks in and out through gaps and openings, so the inside is pressurised or depressurised and every inside face is pushed or pulled. Without better knowledge both Cpi = +0.2 and −0.3 are checked. A large opening in one face (a door left open) makes it dominant and changes Cpi; the calculator can work that out from the opening areas.
outside: qp Cpeinside: qp Cpinet on the wall: w = qp (Cpe − Cpi)
Net pressure. A wall or roof sheet feels the outside pressure minus the inside pressure: w = qp (Cpe − Cpi). Positive pushes inwards, negative pulls outwards.
Cpi = +0.2Cpi = −0.3worst for suction:roofs, side and leewardwalls (uplift)worst for pressure:the windward wall andpositive roof zoneseach element: the worse of the two
The worst combinations. Positive internal pressure adds to external suction; negative internal pressure adds to external pressure. Each element is designed for the worse of the two, and for each wind direction (on the long face and on the gable).
net pressure: w = qp (Cpe − Cpi) Cpi = +0.2 and −0.3, the worse governs frames, purlins: Cpe,10; sheets and fixings (≤ 1 m²): Cpe,1; e = min(b, 2h)

6. Cladding and frames

Cpe,10 for frames and purlins; Cpe,1 for sheets and fixings (≤ 1 m²)corners and edges: much higher local suction
Local coefficients. Small areas such as a sheet, a fixing or a purlin cleat feel the gusty peaks at corners and edges. For loaded areas of 1 m² or less the code gives Cpe,1, much higher than the overall Cpe,10. The calculator lists both.
frame load (kN/m) = w (kPa) × bay width (m)
From pressures to a frame. A portal frame collects the wind from half a bay on each side, so its line load is the net pressure times the frame spacing: on the columns (D and E) and on each part of the rafters (the roof zones it crosses). STATIX gives the pressures; the frame loads are a short hand step.

7. In STATIX

qplesson 4roof typepitch, CpizonesCpe, wworstper element
In the STATIX wind load calculator: after qp, choose the roof type and pitch and the internal pressure (or derive it from openings). It lists every wall and roof zone with Cpe and the net pressure for both Cpi, for wind on the long face and on the gable, and marks the governing ones. It has no topography input (co = 1.0).

8. Example A: the zone pressures of a warehouse

The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.

9. Example B: wind loads on a portal frame

The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.

10. Do it in STATIX

The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.

11. Common mistakes

The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.

12. Exercises

The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.

13. Self-check quiz

The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.

14. Lesson 5 on one page

The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.

Next: Lesson 6, load paths and take-downFrom the roof and floors down the columns to the footing, with the combinations.
Go to lesson 6

A worked example for learning, not a design. Check every value against the current code and your own project, and have the design checked and signed by a registered professional engineer.