Course · lesson 1 of 6

Actions, limit states and combinations

Every design starts with the loads. This lesson sorts the actions on a building, explains characteristic values, limit states and partial factors, and builds the load combinations of SANS 10160-1 the way the STATIX calculators do.

1. Learning outcomes

After this lesson you can:

  • sort the actions on a building into permanent, variable and accidental;
  • explain a characteristic value and the difference between the ultimate and the serviceability limit state;
  • apply the partial factors of SANS 10160-1, including the favourable 0.9 on G;
  • build the combinations with a leading action and ψ on the others, and find the one that governs;
  • enter loads per source in STATIX and read the combinations it makes.

2. Before you start

  • Your copy of SANS 10160-1 (basis of design) and SANS 10160-2 (permanent and imposed loads).
  • The free pad footing calculator: it lists the combinations it makes.
  • A pocket calculator and about 45 minutes.

3. Actions

G: self-weight, finishesQ: people,furniture, storageW: wind
The actions on a building. Permanent actions G (the weight of the structure, finishes and fixed services) are always there. Variable actions come and go: imposed loads Q from use, and wind W. Accidental actions (impact, fire, explosion) have their own rules.
GG + Qa gust (W)timeload
How actions change in time. G is nearly constant for the life of the building; Q changes with use; wind arrives in short gusts. Because Q and W rarely reach their peaks together, the code adds them with a reduced value for the one that does not lead.
characteristicvalueload measured on many buildingssmall chanceof more
The characteristic value. Loads vary from building to building. The characteristic value is set so that only a small fraction of real loads exceed it during the reference period. SANS 10160-2 and -3 give these values: the densities, the imposed loads by category and the basic wind speed.

4. Limit states and partial factors

ultimate (ULS)serviceability (SLS)collapse, rupture,overturningdeflection, cracking,vibrationfactored actionscharacteristic actions
Two kinds of limit state (SANS 10160-1). At the ultimate limit state the structure must not collapse, so the actions are increased by partial factors. At the serviceability limit state it must stay usable, so the actions are taken at about their characteristic values.
G unfavourable (STR)1.2G alone (STR-P)1.35G favourable0.9Q leading (STR)1.6W leading (STR)1.61.0
Partial factors for actions, SANS 10160-1 Table 3. Variable actions get a bigger factor than permanent ones because they are less certain. Where the permanent load helps (holding a roof down against wind uplift), it is reduced to 0.9.

5. Combinations

Galways+leadingfull value+accompanyingψ × valuetry each variable action as the leading one;the worst result governsψ: imposed (offices, homes, shops) 0.3; wind 0
Leading and accompanying actions (SANS 10160-1 7.3.2.1, eq. (6)). One variable action is taken at its full value and the others at a reduced combination value ψ times theirs (Table 2). You repeat this with each variable action leading.
STR, Q leads1.2 G + 1.6 QSTR-P1.35 G + 1.0 QSTR, W leads1.2 G + 1.6 ψQ + 1.6 WSTR, G helps0.9 G + 1.6 WSLSG + Q, G + ψQ + W
The usual set for a building (SANS 10160-1 Table 3 and eq. (10)), as STATIX lists them when G, Q and W are all present. Each line is a separate load case; the structure is checked for all of them.
ULS, STR (Table 3): 1.2 G + 1.6 Qleading + 1.6 ψ Qaccompanying ULS, STR-P: 1.35 G + 1.0 Qleading G favourable: 0.9 G + 1.6 W SLS (eq. (10)): G + Qleading + ψ Qaccompanying
wind lifts the roofits weight holds itdown: take 0.9 Gthe column may endin tension
When G helps. Under wind uplift on a light roof, the permanent load is what keeps the frame down, so it is taken low (0.9 G) with the wind high. The column and its holding-down bolts may then be in tension: a case a G + Q check alone never shows.
1.2G + 1.6Q1.35G + Qall Gall Qshare of Q in the totalfactor on the total
Why STR-P exists. When the permanent load is large and the imposed load small (heavy roofs, thick slabs, retaining structures), 1.35 G + Q gives more than 1.2 G + 1.6 Q. STATIX works out both and the larger governs.
δSLS: G + Q (characteristic), no partial factorsirreversible effects, eq. (10)
Serviceability. Deflection, cracking and vibration are checked with the actions at their characteristic values, the leading variable action in full and the others times ψ. These are the loads the building really carries on a bad day, not the factored ones.

6. In STATIX

G, Q, Wper sourcethe codeSANS 10160-1combinationsULS and SLSthe designevery case
In STATIX you enter the characteristic actions per source, never pre-factored: G, Q and W apart. The calculator builds the code's combinations itself and designs for every one. The pad footing calculator lists them, with the clause for each.

7. Example A: a column in an office block

The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.

8. Example B: a portal frame column with wind

The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.

9. Do it in STATIX

The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.

10. Common mistakes

The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.

11. Exercises

The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.

12. Self-check quiz

The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.

13. Lesson 1 on one page

The worked parts open with a university or college email, a student licence (statix.engineering/university/), a calculator pack or a paid plan. Sign in to open them.

Next: Lesson 2, permanent loadsDensities, finishes, services and walls: building up G for a floor and a wall.
Go to lesson 2

A worked example for learning, not a design. Check every value against the current code and your own project, and have the design checked and signed by a registered professional engineer.