Retaining wall along its length to SANS 10100
A 12 m long reinforced concrete cantilever wall holds back 3 m of granular fill with a 10 kPa surcharge. The wall is designed segment by segment along its length: earth pressure, sliding, overturning and bearing (as global factors of safety and with partial factors), overall stability, the stem and base bars, and early-age cracking. Every result below is what the STATIX retaining wall 3D calculator reports for the values in step 1.
1. The problem
| Input | Value |
|---|---|
| Wall type, code | cantilever, SANS 10100-1 |
| Length / retained height (top of wall to the base underside) | 12 m / 3 m |
| Stem / base thickness | 300 / 400 mm |
| Toe / heel | 700 / 2 000 mm (base width 3.0 m) |
| Front soil over the base | 500 mm |
| Backfill φ′ / γ | 30° (given) / 18 kN/m³ |
| Surcharge | 10 kPa |
| Allowable bearing pressure | 150 kPa (given) |
| Founding soil under the base: φ′ / γ | 30° / 18 kN/m³ (given) |
| Base friction coefficient | 0.45 |
| Passive resistance in front of the toe | ignored (the default) |
| Water behind the wall | none |
| Seismic | none (given) |
| fcu / fy; cover | 30 / 450 MPa; 50 mm (60 mm the base) |
| Early-age temperature drop T1 | 20 °C (given) |
The six values marked given are the ones the calculator asks you to confirm for your site. Leave them as it fills them and a passing wall reads REVIEW, not PASS (step 6).
2. Earth pressure
A cantilever wall can move a little, so the backfill is in the active state. With Rankine’s coefficient:
3. Stability: sliding, overturning and bearing
The wall must not slide, tip or press the soil too hard. The calculator checks these twice: with global factors of safety (SANS 10160-5) and with partial factors on the actions and the soil (the GEO set: G 1.0, Q 1.3, the soil strength factored).
The surcharge on the heel is not counted as resisting: it is a variable load and may be absent. The passive resistance of the soil in front of the toe is not counted either: that soil can be dug away later, so the calculator ignores it unless you include it. Included, it would add 6.75 kN/m here.
| Check | Result | Use |
|---|---|---|
| Sliding, partial factors | governs the wall | 95 % |
| Sliding, global FoS | 1.74 against 1.5 | 86 % |
| Overturning, global FoS | 5.92 against 2.0 | 34 % |
| Bearing pressure | qmax 55.8 kPa against 150 kPa | 37 % |
| Bearing, partial factors | — | 46 % |
| Eccentricity | e 0.055 m ≤ B/6 = 3.0/6 = 0.500 m (no lift at the heel) | 11 % |
| Overall stability (slip circle) | — | 69 % |
Sliding governs, as it often does for a cantilever wall on granular soil. With a 1.8 m heel the same wall would need the passive soil to pass; the 2.0 m heel carries more soil on the base and passes without it. A shear key or a rougher founding layer are the other ways to raise the sliding resistance.
4. The stem and the base
The stem is a cantilever from the base; the toe and the heel are cantilevers from the stem. Without links, the shear decides more often than the bending:
| Check | Use |
|---|---|
| Stem deflection (span / depth, SANS 10100-1 4.3.6) | 91 % |
| Heel shear (4.3.4) | 70 % |
| Stem shear | 43 % |
| Toe shear | 36 % |
| Crack control (bar spacing) | 33 % |
| Stem bending / heel bending / toe bending | 14 % / 16 % / 3 % |
5. Early-age heat and shrinkage
The stem is cast on a base that has already hardened, so the base holds it as it cools and shrinks. EN 1992-3 Annex M:
6. Result, and what REVIEW means
With the six values given, the wall reads PASS; the governing row is sliding with partial factors (95 %). Leave them as the calculator fills them and the same wall reads REVIEW: it names the backfill friction angle and the other values it assumed, and asks you to confirm them. REVIEW is never shown as PASS.
7. Do it in STATIX
Open the retaining wall 3D calculator, type the values in step 1 and compare the rows. For a single cantilever section with its full hand calculation, see the cantilever retaining wall example.
A worked example for learning, not a design. Check every value against the current code and your own project, and have the design checked and signed by a registered professional engineer.