RC wall element under in-plane forces to EN 1992-1-1

A wall or slab element under in-plane forces needs reinforcement in two directions and a concrete strut that is strong enough. Here EN 1992-1-1 Annex F is worked by hand for a 200 mm element under tension, compression and shear. The hand calculation is checked against the STATIX RC membrane element calculator.

1. The problem

InputValue
In-plane forcesn_x = -200 kN/m, n_y = 100 kN/m, n_xy = 300 kN/m (compression positive)
Thicknesst = 200 mm
Concrete / steelf_ck = 30 MPa, f_yk = 500 MPa, α_cc = 0.85
Strut angleoptimum (cot θ left blank)
Steel providednot given: the calculator gives the steel needed

2. The method EN 1992-1-1 Annex F

A wall or slab element carries in-plane forces nx, ny and shear nxy. Annex F replaces it by a concrete compression field and reinforcement along x and y. The reinforcement takes the tension; the concrete strut must not be overstressed. Annex F counts compression as POSITIVE, and so does the calculator.

3. Stresses in the element EN 1992-1-1 Annex F

Divide each force per metre by the thickness. Compression positive: nx = -200 kN/m is tension, ny = 100 kN/m is compression.

σ_Edx = n_x / t = -200 / 200 = -1.00 MPa σ_Edy = n_y / t = 100 / 200 = 0.50 MPa τ_Edxy = n_xy / t = 300 / 200 = 1.50 MPa
σx = -1.00 MPa (tension)σy = 0.50 MPa (comp.)τxy = 1.50 MPax → (y up)t = 200 mm, per metre of wall

4. Order of the axes EN 1992-1-1 Annex F

The Annex F formulas take σEdx ≥ σEdy. Here σy = 0.50 is larger than σx = -1.00, so the axes are swapped for the working: the Annex F x-axis (call it x') is the element's y, and y' is the element's x. The answer is given back on x and y at the end.

σ_x' = 0.50 MPa, σ_y' = -1.00 MPa, |τ| = 1.50 MPa

5. Is reinforcement needed? EN 1992-1-1 F.1(3)

No design reinforcement is needed only when both normal stresses are compressive and σx' σy' > τ². Here σy' is tension, so reinforcement is needed.

σ_y' = -1.00 MPa < 0 → reinforcement needed

6. Reinforcement stresses EN 1992-1-1 F.1(4), eq. F.2 - F.4

With σx' ≤ |τ| the optimum layout (the strut at 45°) gives the tension the steel must carry, per unit area of the element, from F.2 and F.3, and the strut stress from F.4. The case σx' > |τ| (F.5 - F.7) does not apply.

σ_x' = 0.50 ≤ |τ| = 1.50 → F.2 - F.4 f_tdx' = |τ| − σ_x' = 1.50 − 0.50 = 1.00 MPa (F.2) f_tdy' = |τ| − σ_y' = 1.50 − (-1.00) = 2.50 MPa (F.3) σ_cd = 2 |τ| = 2 × 1.50 = 3.00 MPa (F.4)

7. Reinforcement area EN 1992-1-1 F.1(2), eq. F.1

Back on the element's axes: the steel along x takes ftdy' and the steel along y takes ftdx'. ftd = ρ fyd (F.1), so the area per metre is ftd t / fyd, for both faces together. fyd = 500 / 1.15 = 434.78 MPa.

f_tdx = 2.50 MPa, f_tdy = 1.00 MPa A_sx = f_tdx t / f_yd = 2.50 × 200 × 1000 / 434.78 = 1150.0 mm²/m (ρ_x = 0.575 %) A_sy = f_tdy t / f_yd = 1.00 × 200 × 1000 / 434.78 = 460.0 mm²/m (ρ_y = 0.230 %) each face: A_sx / 2 = 575.0 mm²/m, A_sy / 2 = 230.0 mm²/m

8. Concrete compression field EN 1992-1-1 F.1; ν from 6.5.2(2), eq. 6.56 / 6.57N

The cracked concrete strut has a reduced strength σRd,max = 0.6 ν′ fcd, ν′ = 1 − fck / 250 (6.5.2(2), the struts of Annex F); written below as ν fcd with ν = 0.6 (1 − fck / 250). αcc = 0.85 is the calculator's default: a practice value, the National Annex sets it (SANS 51992 uses 1.0).

f_cd = 0.85 × 30 / 1.5 = 17.00 MPa ν = 0.6 × (1 − 30 / 250) = 0.528 σ_cd = 3.00 MPa ≤ ν f_cd = 0.528 × 17.00 = 8.976 MPa OK, utilisation 0.334

9. What is not checked here EN 1992-1-1 F.1(5)

The reinforcement must be fully anchored at every free edge, for example with U-bars (F.1(5)). The minimum wall or slab reinforcement of 9.6 / 9.3 is a separate check. The calculator shows this as a NOT CHECKED row.

10. The calculator's answer

The calculator, with the same inputs, gives (engine 1.0.1): case F.2 - F.4 with the axes swapped, ftdx = 2.50 MPa, ftdy = 1.00 MPa, Asx = 1150.0 mm²/m, Asy = 460.0 mm²/m, σcd = 3.00 MPa ≤ 8.976 MPa, and PASS. The hand calculation gives the same numbers. Set cot θ in the calculator to try a strut angle other than 45° (F.8 - F.10).

Run this example yourselfOpen the STATIX RC membrane element calculator. These are the calculator's default inputs, so it opens on this example. Change any value and the result updates, with every check and a calc sheet.
Open the RC membrane element calculator

A worked example for learning, not a design. Check every value against the current code and your own project, and have the design checked and signed by a registered professional engineer.