A lipped C purlin spans 6 m between rafters and carries a light roof, but the wind lifts it. Here the Direct Strength Method of SANS 10162-2 and the uplift rule of 3.3.3.4 are worked by hand for a C 200 × 75 × 20 × 2.0 in G450 steel. The hand calculation is checked against the STATIX cold-formed purlin calculator.

1. The problem

InputValue
Purlinsimple span L = 6 m, spacing 1.2 m
Sectionlipped channel C 200 × 75 × 20 × 2 mm, inner corner radius 2 mm
SteelG450: f_y = 450 MPa, E = 200000 MPa
Roof loadsg_k = 0.15 kPa, q_k = 0.25 kPa, wind w_k = -0.75 kPa (uplift)
Restrainttop flange screwed to the sheeting, cyclone washers; 1 row of bridging
Factorsφ_b = φ_v = 0.90; k_v = 5.34; deflection limit L / 200

2. The method SANS 10162-2 (AS/NZS 4600) 7.2.2; 3.3.3.4

A thin cold-formed section buckles before it yields. SANS 10162-2 (the same text as AS/NZS 4600:2005) offers the Direct Strength Method (DSM, Section 7): work out the elastic buckling moments of the whole section for local buckling (Mol), distortional buckling (Mod) and global buckling, then read the strength off the DSM curves. Under wind uplift the free bottom flange is in compression and is not held by the sheeting; for a simple-span C or Z with cyclone washers, 3.3.3.4 gives the member capacity as Mb = R Ze fy.

sheeting (screwed, cyclone washers)wind upliftfree flange + lipin compression under upliftD = 200 mmB = 75 mmlip 20 mmt = 2 mm, r_i = 2 mm

3. Section properties SANS 10162-2 (AS/NZS 4600) section properties, linear method

The section is treated as its centreline (a line of thickness t): flat parts plus four 90° corners of centreline radius rc = ri + t / 2. The flats are the web a, the two flanges b and the two lips l; the corners are arcs of length u = π rc / 2 whose centroids sit 2 rc / π past the corner centres. Ix adds each part's own I and its area times its distance² from mid-depth.

r_c = 2 + 2 / 2 = 3 mm, a = 200 − 2(2 + 2) = 192, b = 75 − 2(2 + 2) = 67, l = 20 − (2 + 2) = 16 mm, u = π × 3 / 2 = 4.7124 mm A = t (a + 2b + 2l + 4u) = 2 × (192 + 134 + 32 + 18.8496) = 753.70 mm² web: t a³ / 12 = 2 × 192³ / 12 = 1179648 mm⁴ flanges: 2 t b ((D − t) / 2)² = 2 × 2 × 67 × 99.0² = 2626668 mm⁴ lips: 2 (t l³ / 12 + t l y_l²), y_l = 88.0 mm → 496981 mm⁴ corners: 4 t [(π/4 − 2/π) r_c³ + u y_c²], y_c = 96.0 + 2 × 3 / π = 97.9099 mm → 361429 mm⁴ I_x = 4664726 mm⁴ = 4.6647 × 10⁶ mm⁴ Z_f = I_x / (D / 2) = 46647.3 mm³, M_y = f_y Z_f = 450 × 46647.3 = 20.991 kNm

4. Local buckling SANS 10162-2 (AS/NZS 4600) 7.2.2; plate / element method

The calculator finds the local buckling stress of each flat plate on its own, fcr = k π² E / (12 (1 − ν²)) × (t / b)², using the square-corner centreline widths, and takes the lowest. k = 23.9 for the web in bending, 4.0 for the flange (supported on both edges) and 0.43 for the lip (one free edge). This is a simple estimate in place of a finite strip analysis of the whole section: it leaves out how the plates hold or push each other at the corners.

π² E / (12 (1 − 0.3²)) = 180762.0 MPa web b_w = 198: 23.9 × 180762.0 × (2 / 198)² = 440.79 MPa flange b_f = 73: 4.0 × 180762.0 × (2 / 73)² = 542.73 MPa lip d_l = 19: 0.43 × 180762.0 × (2 / 19)² = 861.25 MPa f_ol = 440.79 MPa (web), M_ol = f_ol Z_f = 440.79 × 46647.3 = 20.562 kNm

5. Distortional buckling AS/NZS 4600 (SANS 10162-2) Appendix D, D3 (Lau & Hancock)

In distortional buckling the compression flange and its lip rotate together about the flange-web corner, held back by the bending stiffness of the web (a rotational spring kφ). Lau and Hancock's closed form treats the flange + lip (square corners, centreline) as a small column on that spring. First the flange + lip properties, about its own centroid:

b_f = 73, d_l = 19 mm: A = (b_f + d_l) t = 184.0 mm², x̄ = (b_f² + 2 b_f d_l) / (2 (b_f + d_l)) = 44.0380 mm, ȳ = d_l² / (2 (b_f + d_l)) = 1.9620 mm J = t³ (b_f + d_l) / 3 = 245.33 mm⁴, I_x = 3913.1 mm⁴, I_y = 105019.1 mm⁴, I_xy = 10455.3 mm⁴ β1 = x̄² + (I_x + I_y) / A = 2531.37 mm² half-wavelength λ = 4.80 (I_x b_f² b_w / (2 t³))^0.25 = 4.80 × (3913.1 × 73² × 198 / (2 × 2³))^0.25 = 608.37 mm, η = (π / λ)² = 2.66663 × 10⁻⁵ mm⁻² α2 = η (I_y + (2 / β1) ȳ b_f I_xy) = 2.83202 first pass, no spring: α1 = (η / β1)(I_x b_f² + 0.039 J λ²) = 0.256975, α3 = η (α1 I_y − (η / β1) I_xy² b_f²) = 0.556011 f_od' = E / (2A) [(α1 + α2) − √((α1 + α2)² − 4 α3)] = 200000 / (2 × 184.0) × [3.08900 − √(3.08900² − 4 × 0.556011)] = 208.61 MPa web spring: k_φ = 2 E t³ / (5.46 (b_w + 0.06 λ)) × [1 − 1.11 f_od' / (E t²) × b_w⁴ λ² / (12.56 λ⁴ + 2.192 b_w⁴ + 13.39 λ² b_w²)] = 2499.25 × [1 − 1.11 × 208.61 / (200000 × 2²) × 296.555] = 2284.7 N mm/rad per mm with the spring: α1 = 0.256975 + k_φ / (β1 η E) = 0.426207, α3 = 1.02994 f_od = 200000 / (2 × 184.0) × [3.25823 − √(3.25823² − 4 × 1.02994)] = 385.57 MPa M_od = f_od Z_f = 385.57 × 46647.3 = 17.986 kNm

6. DSM section strength SANS 10162-2 (AS/NZS 4600) 7.2.2.3, 7.2.2.4

The section strength is the lower of the local and the distortional DSM curves, with the global moment Mbe = My (no lateral buckling counted here: under uplift it is covered by R in the next step). Local: Mbl = Mbe for λl ≤ 0.776, else [1 − 0.15 (Mol/Mbe)0.4](Mol/Mbe)0.4 Mbe. Distortional: Mbd = My for λd ≤ 0.673, else [1 − 0.22 (Mod/My)0.5](Mod/My)0.5 My.

λ_l = √(M_be / M_ol) = √(20.991 / 20.562) = 1.0104 > 0.776 (M_ol / M_be)^0.4 = 0.99177, M_bl = (1 − 0.15 × 0.99177) × 0.99177 × 20.991 = 17.721 kNm λ_d = √(M_y / M_od) = √(20.991 / 17.986) = 1.0803 > 0.673 (M_od / M_y)^0.5 = 0.92565, M_bd = (1 − 0.22 × 0.92565) × 0.92565 × 20.991 = 15.474 kNm M_s = min(M_bl, M_bd) = 15.474 kNm (distortional)

7. Uplift: the free flange in compression SANS 10162-2 3.3.3.4

For a channel or Z with the tension flange screwed to the sheeting and the compression flange unbraced, 3.3.3.4 gives Mb = R Ze fy. For uplift on a simple span with cyclone washers, R = 0.75 with no bridging, 0.85 with one row, 1.00 with two rows. R applies only inside the clause limits, checked below; the sheeting, screw, cleat and bridging conditions (vi) to (xv) are the engineer's to provide. The calculator takes Ze fy as the DSM section strength Ms of the step before (its reading of Ze fy); φb = 0.90 (Table 1.6).

(i) D = 200 ≤ 300 mm, (ii) lipped, (iii) 75 < D/t = 100.0 < 135, (iv) 2.3 < D/B = 2.667 < 3.2, (v) 25 < flat flange / t = (75 − 2(2 + 2)) / 2 = 33.5 < 44, (vii) L = 6 ≤ 10.5 m all met M_b = R M_s = 0.85 × 15.474 = 13.153 kNm, φ_b M_b = 0.90 × 13.153 = 11.837 kNm

8. Loads and moments SANS 10160-1 Table 3

The roof loads per square metre times the purlin spacing give line loads: G = 0.18, Q = 0.30 and W = −0.90 kN/m (minus = uplift). The calculator runs every combination of SANS 10160-1 Table 3 (the imposed roof load has ψ = 0 with wind) and keeps the worst. On a simple span M* = w* L² / 8. Downward loads put the screwed top flange in compression (φ Mb = 0.90 Ms); uplift puts the free flange in compression (φ Mb from the step before).

1.2G + 1.6Q w* = 0.696 kN/m M* = 3.132 kNm φM_b = 13.93 kNm 23 % 1.35G + 1.0Q w* = 0.543 kN/m M* = 2.443 kNm φM_b = 13.93 kNm 18 % 0.9G + 1.6W w* = −1.278 kN/m (uplift) M* = 5.751 kNm φM_b = 11.84 kNm 49 % 1.2G + 1.6W w* = −1.224 kN/m (uplift) M* = 5.508 kNm φM_b = 11.84 kNm 47 % governing 0.9G + 1.6W: w* = 0.9 × 0.18 + 1.6 × (−0.90) = −1.278 kN/m M* = 1.278 × 6² / 8 = 5.751 kNm ≤ 11.837 kNm OK, 49 %

9. Shear in the web SANS 10162-2 3.3.4

The flat web, hw = D − 2(t + ri), carries the shear. Its yield shear is 0.6 fy Aw and its elastic buckling shear Aw fcr with kv = 5.34 (unstiffened web). The slenderness λv = √(Vy / Vcr) picks the curve: Vy up to 0.815, 0.815 √(Vcr Vy) up to 1.227, Vcr beyond.

h_w = 200 − 2 × (2 + 2) = 192 mm, A_w = 192 × 2 = 384 mm² f_cr = 5.34 π² E / (12 (1 − 0.3²)(h_w / t)²) = 5.34 × 180762.0 / 96.0² = 104.738 MPa V_y = 0.6 × 450 × 384 = 103.68 kN, V_cr = 384 × 104.738 = 40.220 kN, λ_v = √(103.68 / 40.220) = 1.606 > 1.227 → V_v = V_cr V* = w* L / 2 = 1.278 × 6 / 2 = 3.834 kN ≤ φ_v V_v = 0.90 × 40.220 = 36.20 kN OK, 11 % (the calculator adds a bending + shear check (3.3.5) only when both ratios exceed 0.3; here the shear ratio is 11 %)

10. Deflection SANS 10160-1 eq. (10); limit L / 200 (practice value)

The deflection uses the service loads and the gross Ix: dead + imposed, and dead + wind (SANS 10160-1 eq. (10), ψ = 0 for the roof load), the larger one checked. The limit L / 200 is the page's default, a practice value for purlins under a metal roof, not a code number; agree it for your project.

G + Q: 5 × 0.48 × 6000⁴ / (384 × 200000 × 4664726) = 8.68 mm G + W: 5 × |0.18 − 0.90| × 6000⁴ / (384 × 200000 × 4664726) = 13.02 mm δ = 13.02 mm ≤ L / 200 = 30.0 mm OK, 44 %

11. The calculator's answer

The calculator, with the same inputs, gives φ Mb = 11.84 kNm under uplift (R 0.85), M* = 5.75 kNm, 0.9G + 1.6W governs at 49 % and PASS (engine cold-formed-purlin-engine.js, git 62183159; the engine has no version number of its own). The hand calculation gives the same. Set the bridging to none (R = 0.75) or take the cyclone washers away in the calculator: without them 3.3.3.4 gives no R, and the calculator turns to a finite strip analysis instead.

hand: M_y = 20.991, M_ol = 20.562, f_od = 385.57 MPa, M_od = 17.986, M_s = 15.474, φM_b = 11.837 kNm; φV_v = 36.20 kN; δ = 13.02 mm calculator: M_y = 20.991, M_ol = 20.562, f_od = 385.57 MPa, M_od = 17.986, M_s = 15.474, φM_b = 11.837 kNm; φV_v = 36.20 kN; δ = 13.02 mm
Run this example yourselfOpen the STATIX cold-formed purlin calculator. These are the calculator's default inputs, so it opens on this example. Change any value and the result updates, with every check and a calc sheet.
Open the cold-formed purlin calculator

A worked example for learning, not a design. Check every value against the current code and your own project, and have the design checked and signed by a registered professional engineer.